上一(yī)篇:JGH上(shàng)海(hǎi)剛(gāng)體滑觸綫廠家上海(hǎi)徐吉(jí)
下一篇:HXPnL-T上(shàng)海耐高溫(wēn)(剛(gāng)體(tǐ))鋼體(tǐ)滑觸綫廠(chǎng)家
歡(huān)迎訪問上海徐吉電(diàn)氣(qì)有(yǒu)限公司(sī)網站(zhàn)

產品型(xíng)號:JGD
廠商(shāng)性(xìng)質(zhì):生產(chǎn)廠(chǎng)家
所(suǒ)在地:上海市
更新時(shí)間:2023-12-21
產品簡介(jiè):
耐高溫(剛體(tǐ))鋼(gāng)體(tǐ)滑(huá)觸綫(xiàn)
一:HXPnL-T,HXPnL-TⅡ,HXPnL-TⅢ係列鋼體滑綫(xiàn)由銅(tóng)導(dǎo)軌,導軌支架(jià),絕緣(yuán)子組(zǔ)件(jiàn)以(yǐ)及外(wài)置(zhì)式(shì)集(jí)電(diàn)器等組件組(zǔ)合(hé)而成(chéng),由於(yú)該(gāi)產(chǎn)品(pǐn)具有電流(liú)大(dà),耐(nài)高(gāo)溫(wēn),抗腐蝕等(děng)特點(diǎn),因(yīn)此被(bèi)廣泛(fàn)應用(yòng)於冶(yě)金,造船,港口(kǒu)等行業.
HXPnL-T係(xì)列鋼(gāng)體(tǐ)滑綫(xiàn)
HXPnL-T Serise steel collector bar | |||||
型號(hào)規(guī)格 Type & spec | 滑(huá)觸綫(xiàn)截麵(miàn)尺寸(cùn)(mm)Busbar size (mm) | 載流量(A) Current(A) | 適(shì)配外置式集電器(qì) Suit able current collenctor | ||
A | B | C | |||
HXPnL-T-85/300 | 48 | 56 | 13.42 | 300 | TJD-600 |
HXPnL-T-110/400 | 50 | 56 | 14.11 | 400 | TJD-600 |
HXPnL-T-170/500 | 55 | 56 | 15.88 | 500 | TJD-600 |
HXPnL-T-240/700 | 58 | 56 | 16.93 | 700 | TJD-600 |
HXPnL-T-320/900 | 63 | 56 | 18.7 | 900 | TJD-600 |
HXPnL-TⅡ-170/1000 | 65 | 80 | 46 | 1000 | TJD-1200 |
HXPnL-TⅡ-240/1300 | 68 | 80 | 46 | 1300 | TJD-1200 |
HXPnL-TⅡ-320/1900 | 73 | 80 | 50 | 1900 | TJD-1200 |
注:滑觸綫(xiàn)標準長度:6m。 Note:standard busbar length 6m. | |||||

一,產品特點
本(běn)產品由(yóu)梯(tī)型(xíng)銅棒和槽(cáo)鋼(gāng)或由“T”型(xíng)銅(tóng)排和槽(cáo)型(xíng)鋁(lǚ)結合(hé)相(xiāng)構成。用(yòng)高強(qiáng)度(dù)絕緣(yuán)子(zǐ)作支撐,從(cóng)而(ér)組(zǔ)成(chéng)向(xiàng)各(gè)種(zhǒng)起(qǐ)重(zhòng)機(jī)械(xiè)設備(bèi)饋(kuì)電的移動滑觸綫。本產(chǎn)品有(yǒu)如(rú)下(xià)特點(diǎn):
1,運行可(kě)靠,絕(jué)不發生電源(yuán)中斷(duàn)故(gù)障。
2,可(kě)使用(yòng)於高(gāo)溫,高(gāo)粉塵,高(gāo)腐(fǔ)蝕(shí)氣體(tǐ)等惡劣環(huán)境(jìng)。
3,機械強度大,不易彎曲變(biàn)形(xíng),能耐(nài)受*的短路衝擊(jī)電流(liú)。
4,可根據用戶需(xū)要設(shè)定(dìng)載流量(liáng),zui大可(kě)達3000A以上,電壓(yā)等(děng)級可達到(dào)5KV以上。
5,采(cǎi)用(yòng)銅或銅鋁導體,可(kě)大(dà)幅度(dù)降低導綫(xiàn)電(diàn)能損耗(hào)。
6,添加輔助電(diàn)纜(lǎn)後,可(kě)組(zǔ)成低阻(zǔ)抗滑觸綫,導綫阻(zǔ)抗成倍(bèi)降低。
7,布(bù)綫可在上部(bù)或下部(bù)滑(huá)觸(chù)。
8,JGH-“I”型滑(huá)觸綫更(gēng)有(yǒu)散(sàn)熱麵特大,結(jié)構緊湊簡單(dān),安(ān)裝(zhuāng)維修(xiū)方(fāng)便(biàn)等(děng)優點。
二(èr),產品型號(hào)與(yǔ)規(guī)格(gé)
鋼(gāng)體滑觸(chù)綫型號(hào),規格(gé)及(jí)額(é)定電(diàn)流(liú)值
型號 | 標(biāo)稱截(jié)麵 | 額定(dìng)電壓(A) | 重(zhòng)量(Kg/6m) |
JGH-85 | 85 | 500 | 24.3 |
JGH-110 | 110 | 600 | 25.9 |
JGH-170 | 170 | 800 | 29.4 |
JGH-240 | 240 | 1000 | 46.1 |
JGH-320 | 320 | 1200 | 50.4 |
JGH-170Ⅱ | 2x170 | 1300 | 53.9 |
JGH-240Ⅱ | 2x240 | 1800 | 62.2 |
JGH-320Ⅱ | 2x320 | 2200 | 68.8 |
注(zhù):滑觸綫標準(zhǔn)長(cháng)度(dù):6m,可根據用戶需(xū)求(qiú)設置(zhì)載(zǎi)流(liú)量(liáng),zui大可達3000A以上。 | |||
型(xíng)號(hào) | 標(biāo)稱(chēng)截麵 | 額定(dìng)電壓(A) | 重(zhòng)量(Kg/6m) |
JGHI-10 | 85 | 500 | 24.3 |
JGHI-110 | 110 | 600 | 25.9 |
JGHI-170 | 170 | 800 | 29.4 |
JGHI-240 | 240 | 1000 | 46.1 |
JGHI-320 | 320 | 1200 | 50.4 |
JGHI-170Ⅱ | 2x170 | 1300 | 53.9 |
JGHI-240Ⅱ | 2x240 | 1800 | 62.2 |
JGHI-320Ⅱ | 2x320 | 2200 | 68.8 |
鋼體滑(huá)觸(chù)綫一般情(qíng)況下按6m定尺長度供貨。
鋼(gāng)體滑觸綫絕緣(yuán)支(zhī)架安(ān)裝間(jiān)距一(yī)般(bān)為3m
滑(huá)觸(chù)綫分為(wéi)單綫式和雙綫(xiàn)平(píng)等饋(kuì)電(diàn)式兩(liǎng)種(zhǒng),除(chú)雙綫(xiàn)平等(děng)式(shì)以JGH-□II表(biǎo)示(shì)外,單綫(xiàn)式不(bù)另(lìng)加表注,其斷麵(miàn)如下:
三,鋼體(tǐ)滑觸綫(xiàn)係列配(pèi)套件
D集電(diàn)器
|
四(sì),鋼(gāng)體滑觸綫的(dí)連(lián)接
滑(huá)觸(chù)綫的(dí)連接如(rú)下(xià)圖(tú)所示:
連接時,將(jiāng)兩(liǎng)段(duàn)支架(jià),通(tōng)過(guò)內部(bù)的鋼芯用螺(luó)栓(shuān)連(lián)接,銅(tóng)導體則(zé)用(yòng)二塊(kuài)長夾板(bǎn),夾緊(jǐn)在(zài)支架上,為了(liǎo)防止(zhǐ)剛體(tǐ)因(yīn)溫(wēn)度變化(huà)引起(qǐ)的膨(péng)脹,安(ān)裝(zhuāng)時(shí)在連接處應(yīng)留有(yǒu)間(jiān)隙(xì),間隙的(dí)尺寸見(jiàn)下表:
工(gōng)作(zuò)場(cháng)地的(dí)周(zhōu)圍溫(wēn)度(dù) | 30°C | 40°C | 60°C | 70°C |
間隙尺(chǐ)寸 | 3-5mm | 5-7mm | 7-9mm | 10-15mm |
予留間(jiān)隙(xì)的(dí)尺(chǐ)寸(cùn)跟安裝時的(dí)環境溫(wēn)度有關(guān),一般(bān)冬(dōng)季安裝(zhuāng)時(shí)取(qǔ)高值(zhí),夏天安裝時取(qǔ)低值(zhí)。
五,滑(huá)觸綫(xiàn)的安裝(zhuāng)
滑觸綫的(dí)安(ān)裝(zhuāng)方式(shì),一般(bān)常(cháng)用(yòng)的為上(shàng)部滑觸和下部(bù)滑觸二種,也可(kě)根據用(yòng)戶要求,采用其(qí)它(tā)安裝(zhuāng)方式(shì)。
滑觸綫的(dí)安裝支(zhī)架一般為(wéi)3m一(yī)個,特(tè)殊情況亦(yì)可(kě)采取加強措(cuò)施(shī)適(shì)當(dāng)擴(kuò)大距(jù)離(lí),三(sān)根滑觸綫之間的(dí)相(xiāng)間距(jù)離(lí)為400mm,如為低阻(zǔ)抗滑觸(chù)綫,相間(jiān)距離可(kě)擴(kuò)大(dà)到(dào)450mm。
六,鋼體滑觸綫的(dí)設(shè)計(jì)數據及(jí)計(jì)算方式
1,滑(huá)觸(chù)綫阻抗值(zhí)及(jí)100A-100m時(shí)的(dí)綫路電壓(yā)降值(使(shǐ)用(yòng)電(diàn)壓為380V,COS為(wéi)0.8時(shí))
滑(huá)觸綫(xiàn)規格 | 相(xiāng)間距離 | 在(zài)90°C時阻降(jiàng)值(zhí)Z | 100A-100m時(shí)綫路電壓降 | |
u(V) | u% | |||
85 | 200 | 0.3629 | 6.29V | 1.65% |
300 | 0.3813 | 6060V | 1.73% | |
400 | 0.3946 | 6084V | 1.80% | |
110 | 200 | 0.3202 | 5.55V | 1.16% |
300 | 0.3404 | 5.90V | 1.55% | |
400 | 0.3552 | 6.15V | 1.62% | |
170 | 200 | 0.2690 | 4.66V | 1.23% |
300 | 0.2915 | 5.05V | 1.33% | |
400 | 0.3078 | 5.33V | 1.40% | |
240 | 200 | 0.2459 | 4.26V | 1.12% |
300 | 0.2716 | 4.70V | 1.24% | |
400 | 0.2857 | 4.95V | 1.30% | |
320 | 200 | 0.2328 | 4.03V | 1.06% |
300 | 0.2596 | 4.50V | 1.18% | |
400 | 0.2741 | 4.75V | 1.25% | |
2×170 | 200 | 0.2076 | 3.60V | 0.95% |
300 | 0.2319 | 4.02V | 1.06% | |
400 | 0.2493 | 4.32V | 1.14% | |
2×240 | 200 | 0.1976 | 3.42V | 0.90% |
300 | 0.2249 | 3.90V | 1.03% | |
400 | 0.2416 | 4.19V | 1.10% | |
2×320 | 200 | 0.1932 | 3.35V | 0.88% |
300 | 0.2178 | 3.77V | 0.99% | |
400 | 0.2046 | 4.06V | 1.07% | |
2,滑觸綫在短路時(shí)耐受(shòu)電流值(KA)(安(ān)裝(zhuāng)支架間距(jù)為(wéi)3m時(shí))
滑觸綫(xiàn)規(guī)格(gé) | 滑觸綫三相平(píng)放時相間距離(lí)為(wéi) | 滑(huá)觸(chù)綫三(sān)相豎放時相(xiāng)間距離為 | ||||
200mm | 300mm | 400mm | 200mm | 300mm | 400mm | |
85 | 22 | 26 | 31 | 29 | 35 | 41 |
110 | 23 | 27 | 32 | 30 | 36 | 42 |
170 | 25 | 30 | 35 | 32 | 39 | 45 |
240 | 41 | >50 | >50 | >50 | >50 | >50 |
320 | 43 | |||||
2×170 | >50 | |||||
2×240 | ||||||
2×320 | ||||||
3,鋼(gāng)體滑觸綫的(dí)撓度量(mm)
滑(huá)觸綫(xiàn)規格 | 滑(huá)觸綫三(sān)相豎放時(shí),支架間距離為 | 滑觸綫(xiàn)三相(xiāng)平放(fàng)時,支架(jià)間距離(lí)為 | ||||||
2m | 3m | 4m | 5m | 2m | 3m | 4m | 5m | |
85 | 0.28 | 1.44 | 4.6 | 11.1 | 0.33 | 1.62 | 5.14 | 12.6 |
110 | 0.31 | 1.52 | 4.8 | 11.8 | 0.35 | 1.72 | 5.44 | 13.2 |
170 | 0.35 | 1.73 | 5.4 | 13.5 | 0.38 | 1.96 | 6.17 | 15.0 |
240 | 0.16 | 0.84 | 2.3 | 5.4 | 0.20 | 1.08 | 3.20 | 7.8 |
320 | 0.19 | 0.96 | 2.4 | 5.9 | 0.24 | 1.20 | 3.60 | 8.4 |
2×170 | 0.22 | 1.09 | 3.5 | 8.5 | 0.17 | 0.86 | 2.70 | 6.6 |
2×240 | 0.16 | 0.79 | 2.5 | 6.1 | 0.22 | 1.12 | 3.50 | 8.5 |
2×320 | 0.18 | 0.91 | 2.9 | 7.1 | 0.25 | 1.28 | 4.10 | 10.0 |
4,負(fù)荷(hé)電流計算(suàn)
滑觸綫負(fù)荷電流(liú)計算方法,過(guò)去采用二(èr)項公式(shì)計算(suàn)。現(xiàn)介(jiè)紹(shào)國外多數(shù)資(zī)料(liào)中(zhōng)采用的計算方式(shì)如下(xià):即根據起重機(jī)上安(ān)裝(zhuāng)的有可(kě)能同(tóng)時(shí)運轉(zhuǎn)的(dí)電(diàn)動機(jī)和額定(dìng)電流(liú)乘以暫載係數和多台(tái)起(qǐ)重機(jī)的同(tóng)時係數。
負荷(hé)電(diàn)流(I)=所有工作電動機額(é)定電流(liú)(1H)×暫載(zǎi)係(xì)數(shù)(FED)×同(tóng)時(shí)係數(F)
FED暫載係數(shù)按(àn)下表確定(dìng):(多台(tái)起重(zhòng)機(jī)同時工作(zuò)係數(shù):F取0.4-0.7)
暫載率(shuài)(ED) | 暫(zàn)載率(shuài)(FED) |
100% | 1.00 |
80% | 0.90 |
60% | 0.78 |
50% | 0.71 |
40% | 0.63 |
5,滑觸(chù)綫(xiàn)路的電壓(yā)降(jiàng)問(wèn)題(tí)
過(guò)去設(shè)計滑(huá)觸(chù)綫(xiàn)路(lù)時(shí),采用zui大電流(liú)來檢(jiǎn)驗電(diàn)壓降。即(jí)從低(dī)壓(yā)屏上的饋電形狀(zhuàng)到滑(huá)觸綫取末(mò)端(duān),包括供電(diàn)電纜(lǎn)在(zài)內的電(diàn)壓降不(bù)得超過12%,也就是滑觸綫(xiàn)和供電綫 路(lù)當(dāng)作一(yī)個整體來(lái)考(kǎo)慮,在滿(mǎn)足電壓降的(dí)要求下,務使投資zui少。隨(suí)著近(jìn)年來(lái)引進(jìn)工(gōng)程增多,綜合國(guó)外資料(liào),國(guó)外(wài)一般都(dū)以負(fù)荷(hé)計算(suàn)電流來檢(jiǎn)驗(yàn)電(diàn)壓(yā)降(jiàng),包括供電綫 路在(zài)內(nèi)到滑觸綫zui末的(dí)電(diàn)壓(yā)降值不(bù)得超過5%。
電壓(yā)計算(suàn)公(gōng)式:
u=√ 3 × I×I×Z 或 u=√ 3 × I×I×(RCOSρ+XSinΨ)
式中(zhōng): u=電(diàn)壓(yā)降(jiàng)(V), I=負荷計算(suàn)電流(V), R=電阻(zǔ)(Ω/km)
X=電感(Ω/km), Z=阻(zǔ)抗(Ω/km), L=滑觸(chù)綫諸長度(m)
滑觸綫計(jì)算長(cháng)度(dù)方(fāng)式(shì):為(wéi)滑(huá)觸綫(xiàn)全長(cháng)(m)
在滑(huá)觸綫(xiàn)端(duān)部供電時(shí):I=L
在滑觸綫中部供(gōng)電時:I=L/2
在滑(huá)觸(chù)綫兩端(duān)部同時(shí)供電時(shí):I=L/4
在滑觸(chù)綫兩端端(duān)部距L/6處(chǔ)供(gōng)電時:I=L/6
七,低(dī)阻(zǔ)抗(kàng)滑觸綫(xiàn)
近代(dài)工業中,起(qǐ)重機(jī)噸(dūn)位(wèi)日益(yì)增(zēng)大,運(yùn)行(háng)距(jù)離也愈來愈長,如何(hé)處理(lǐ)滑觸綫(xiàn)上的(dí)電壓降不超(chāo)過允許(xǔ)值(zhí)問(wèn)題(tí),需(xū)要(yào)設(shè)計過程中妥善解(jiě)決(jué)。過(guò)去(qù)解(jiě)決電壓(yā)降過大(dà)的(dí)方(fāng)法(fǎ), 不外(wài)乎(hū)采(cǎi)用:加(jiā)大滑(huá)觸綫(xiàn)和供電綫路的截麵(miàn);增加滑觸(chù)綫(xiàn)上(shàng)的(dí)供(gōng)電(diàn)點(diǎn)數(shù);縮(suō)小三(sān)根滑觸(chù)綫之間的(dí)相間(jiān)距(jù)離(lí)等等(děng),但(dàn)這些(xiē)措施往(wǎng)往收(shōu)效(xiào)甚微或(huò)很(hěn)不(bù)經(jīng)濟,這是因為(wéi)滑觸 綫(xiàn)路(lù)中的電(diàn)抗(kàng)值難(nán)以降低(dī),所(suǒ)以首先(xiān)要(yào)解決(jué)如何(hé)減(jiǎn)少滑(huá)觸綫路上的(dí)電(diàn)抗值著(zhuó)手。本廠同(tóng)有關(guān)設計單(dān)位(wèi)一起,研(yán)究國外資料(liào),在(zài)剛體滑(huá)觸(chù)綫上的(dí)基礎(chǔ)上,添(tiān)加(jiā)兩根(gēn)輔(fǔ)助 電纜,組(zǔ)成低(dī)阻(zǔ)抗滑觸(chù)綫後,可使綫路(lù)阻(zǔ)抗值(zhí)成倍地降低(根據不(bù)同(tóng)規格(gé)的剛(gāng)體添加不同(tóng)截麵的電纜(lǎn)後,其阻抗值(zhí)可(kě)以(yǐ)降(jiàng)低到原來的1/2-1/3)